烟塔合一自然通风冷却塔的有限元分析

FINITE ELEMENT ANALYSIS OF A NATURAL DRAFT COOLING TOWER WITH FLUE GAS INLETS INTEGRATED

  • 摘要: 应用ANSYS有限元软件对浙江省拟建最高烟塔合一冷却塔的内力及线性稳定性进行了分析. 计算表明, 在72^\circ风向角风压作用下在孔口附近产生局部屈曲,使临界风速急剧下降,而在孔口附近经局部加厚处理可消除局部屈曲现象.

     

    Abstract: The commercial software ANSYS is used to analyze thestress and linear stability of the highest naturaldraft cooling tower with flue gas inlets integrated, which will be built in Zhejiang province. The phenomenaof local instability around the hole is found and the critical wind speeddecreases dramatically when the natural draft cooling tower is acted bya 72 degree wind load. This phenomena will disappear when the natural draftcooling tower is thickened around the hole.

     

/